Note publique d'information : LA PRESENTE ETUDE CONCERNE LE TRAITEMENT, PAR LAVAGE BASIQUE OXYDANT, DE L'HYDROGENE
SULFURE PRESENT EN STATION D'EPURATION. L'OXYDANT, LE CHLORE, EST INJECTE SOUS FORME
D'EAU DE JAVEL, OU GENERE ELECTROCHIMIQUEMENT PAR ELECTROLYSE D'UNE SAUMURE. DANS
CE TRAVAIL, NOUS PROPOSONS LA MISE EN UVRE D'UNE ELECTROCHLORATION INTERNE A LA TOUR
DE LAVAGE. LA PREMIERE PARTIE DE L'ETUDE EST CONSACREE A DES RAPPELS BIBLIOGRAPHIQUES
SUR LE TRAITEMENT DES ODEURS ET LA CHIMIE DU SOUFRE ET DU CHLORE, CEPENDANT QUE LA
DEUXIEME TRAITE, DE MANIERE THEORIQUE ET EXPERIMENTALE, L'ABSORPTION DE L'HYDROGENE
SULFURE EN SOLUTION BASIQUE TAMPONNEE. LA DETERMINATION DES FACTEURS D'ACCELERATION
DE TRANSFERT PERMET DE DEMONTRER LA COMPLEXITE DES PHENOMENES LORSQUE LE GAZ CARBONIQUE
ET L'OXYGENE, TOUJOURS PRESENTS DANS L'AIR A DESODORISER, S'ABSORBENT SIMULTANEMENT.
DANS LA TROISIEME PARTIE, L'ETUDE VOLTAMPEROMETRIQUE SUR DSA REVELE L'EFFET NEFASTE
DES IONS HYDROGENOCARBONATES, ET SURTOUT CARBONATES, SUR L'OXYDATION DES CHLORURES,
ET FAIT APPARAITRE LA POSSIBILITE D'OXYDER DIRECTEMENT L'HYDROGENE SULFURE EN SOUFRE
ET POLYSULFURES. LA DETERMINATION DU RENDEMENT FARADIQUE MONTRE QUE LA GENERATION
INDUSTRIELLE DU CHLORURE PAR ELECTROLYSE EST POSSIBLE, AVEC UN BON RENDEMENT A PH
9; A PH 11, EN REVANCHE, UNE TELLE GENERATION N'EST PAS ENVISAGEABLE SUR DSA, ET MOINS
ENCORE SUR GRAPHITE. ENFIN, LA COMPARAISON DES TROIS TECHNIQUES DE COUPLAGE ABSORPTION-OXYDATION
(EAU DE JAVEL, ELECTROCHLORATION EXTERNE OU INTERNE A LA TOUR) MONTRE QUE SEULEMENT
EN SOUS-STCHIOMETRIE, L'ELECTROCHLORATION ET SINGULIEREMENT L'ELECTROCHLORATION INTERNE
EST PLUS EFFICACE QUE L'INJECTION D'EAU DE JAVEL. A PH 9, CETTE NOUVELLE TECHNIQUE
PERMETTRAIT DE RESORBER LES POINTES DE CONCENTRATION EN POLLUANT. PAR AILLEURS, LE
CHLORE GAZEUX LIBERE DANS CE PROCEDE, POURRAIT COUVRIR LES BESOINS EN CHLORE D'UNE
DERNIERE TOUR A PH 11, GENERALEMENT UTILISEE DANS LE PROCEDE GLOBAL DE DESODORISATION